Storage-Tank Overfill (High-Level)

A gauge that stuck, a trip that was defeated, and a tank that kept filling.

What happened

A tank is being filled while its level gauge stops updating and the independent high-level cutoff isn't working. The tank overflows, a large flammable vapor cloud forms at ground level, and finds ignition.

Why it matters

Buncefield (11 December 2005): tank 912 overfilled ~300 tonnes of gasoline; the gauge had stuck (a known intermittent fault) and the independent high-level switch was inoperable because a required padlock was never fitted. The vapor cloud exploded — one of Europe's largest peacetime explosions (Buncefield MIIB report).

Control sequence
  1. Confirm the high-level trip is functional BEFORE starting the transfer.
  2. Cross-check level by independent means during filling (volume balance, timing, manual gauging).
  3. Treat a non-moving gauge during an active fill as failed, not fine.
  4. Stop the transfer at the first unresolvable discrepancy.
How often

Insurance-industry data: overfills occur about once per 3,300 tank fillings — the statistic behind API 2350's overfill-prevention requirements (Emerson, The Complete Guide to API 2350,…

Consequences

Overflow, ground-level vapor cloud (~360 m diameter at Buncefield before igniting ~22 minutes after first CCTV sighting), explosion and multi-tank fire; Buncefield injured 43 and destroyed the terminal (Buncefield MIIB).

Evidence gate: publish only after verification

  • ~1 overfill per 3,300 fillings (insurance data underpinning API 2350). (Emerson/API 2350 guide)cited
  • Buncefield: ~300 t spilled; gauge stuck; high-level switch inoperable for want of a padlock. (MIIB)cited