CloseUtilities & Support Failures
Everyone thought the valve would close. On loss of air, it opened.
A single air-operated control valve loses its air or signal and goes to its spring fail position — but that position turns out to be wrong for the current operating mode, dumping feed forward or blocking an outlet with the pump still running.
CCPS documents a real incident where different fail positions under loss-of-signal vs loss-of-air over-pressurised very large vessels during shutdown, with loss of containment near an occupied building ; guidance stresses identifying the correct fail position for every safety-critical valve, and warns a "fail-open"…
LOPA practice treats a BPCS instrument-loop/control failure as ~1×10⁻¹ per year per loop (dangerous failure rate ≥1×10⁻⁵/hr for non-IEC-61511 BPCS) (HAZOP360 LOPA initiating-event guidance,…
Over-pressurisation of vessels, blocked-outlet transients, runaway feed-forward flow, and loss of containment near occupied areas (CCPS China 2014 incident paper).